Howard Lighting EP2/75IS/MV/SC 75W 2 Lamp F96T12 Electronic Fluorescent Ballast
- UL Listed
- Operates on 120-277V AC Circuits
- Sound class rated A
- 32�F minimum lamp starting temperature for primary lamp
- Primary Lamp Bulb F96T12
Ballast Specifications
- Ballast shall have a five-year warranty
- Ballast shall be UL certified
- Ballast shall be sound rated Class A
- Ballast shall be Class P Type 1 Outdoor
- Ballast shall have a Lamp Current Crest Factor of <1.7
- Ballast shall meet ANSI Standards C62.41-2002 & C82.11-2002
- Ballast shall comply with the limits of FCC Part 18 Class A
- Ballast shall have a lamp operating frequency great than 20kHz
- Ballast shall have a 0oC minimum lamp starting temperature for primary lamp
- Ballast shall be Instant Start
- Ballast shall be Parallel Lamp Operation
- Ballast shall have minimum Power Factor of 99% for primary Lamp operation
- Ballast shall operate within +/- 10% of the ballast specified line voltage at 60 Hz
- Ballast shall have a maximum case hot spot temperature of 90 Celsius